ATF80 Series
ALIA
ATF80 Series
Datasheet (PDF) ↗Target flowmeter
A capacitance sensor detects the deflection caused by flow acting on a target. Suitable configurations include low-velocity gas and steam measurement.
SKU: AN2032
Add to quotation list +Technical specifications
| Measuring range | Steam: 0.002-3400000 t/hr Gas: 1-3280000 Nm3/hr Liquid: 0.1-55800 m3/hr |
|---|---|
| Material | Stainless Steel 304 / 316 |
| Accuracy | Wafer / Flange Type: +/-0.75% of reading Insertion Type: +/-1.6% of reading |
| Repeatability | +/-0.05% FS |
| Multiple flow ranges | 1-3 flow range |
| Process connection | Flange / Wafer / Insertion |
| Flange type | JIS 10K / JIS 20K / JIS 40K ANSI 150# / ANSI 300# / ANSI 600# PN10 / PN16 / PN25 / PN40 |
| Ambient temperature | -25~70 °C |
| Temperature effect | ≤±1% per 50 °C |
| Maximum pressure | 100 bar |
| Operating temperature | Flange / Wafer: -60~450 °C Insertion: -60~450 °C |
| Hot-tappable / retractable construction | -20~80 °C |
| Local indicator | 4 Lines LCD (with backlight) 5 Digit flowrate 8 Digit totalizer |
| Current output | 4-20 mA (2-Wire) Load: Rohm= (VDC-10) * 50 |
| Alarm function | High / Low Alarm |
| Rangeability | 15:1 |
| Communication | HART signal (Compatible) |
| Data retention | Operation parameter and totalizer figures are stored by EEPROM for more than 10 years |
| Body material | Aluminum alloy |
| Cable entry | Standard: M20 Option: 1/2" NPTF |
| Power supply | 10-32 VDC |
| Power supply effect | ≤0.01% / V |
| Keypad | 3 Internal keys for programming and display control |
| Low-flow cut-off | 0-20% |
| Damping | 0-32 Seconds |
| Ingress protection | IP67 Intrinsically Safe, Eex ia IIC T4 Explosion Proof, Ex d IIC T6 |