AMC3200E Series
ALIA
AMC3200E Series
Datasheet (PDF) ↗Electromagnetic flow and energy converter
Calculates thermal energy from the flow measured by an ALIA AMF sensor together with supply and return temperatures. It monitors flow, energy and totals in heating and cooling systems.
SKU: AN2004
Add to quotation list +Technical specifications
| Excitation | DC Plused |
|---|---|
| Display | 4 Lines LCD with backlight Line 1: Date and Time Line 2: 5 Digit flowrate, 6 Digit energy value, Error code, Supply temperature Line 3: 9 Digit totalizer for forward flow / reverse flow, 9 Digit totalizer for heat / cold energy, Error code content, Return temperature Line 4: Differential temperature Unit: L/s, L/min, L/hr, m3/s, m3/min, m3/hr, mL/hr, mL/min, mL/s, kW, MW, KJ/hr, MJ/hr, GJ/hr, Mcal/hr, Kcal/hr, Cal/hr, BTU/hr |
| Measuring range | Min. 0-0.15 m/s Max. 0-15 m/s |
| Accuracy | ±0.2% of reading (velocity ≥0.5 m/s); ±0.001 m/s (velocity <0.5 m/s) |
| Repeatability | +/-0.05% of reading |
| Current output | 4-20 mA (Isolated) Load: Max. 600 Ω |
| Pulse output | Open Collector Rating: 3-30 VDC, 50 mA Max. |
| Pulse frequency | 1) Scaled pulse, (L/Pulse, Other) 2) Frequency: 0-5000 Hz |
| Communication | Bluetooth (Apply to Android System) RS485 (MODBUS Protocol) / BACnet |
| Keypad | 3 External keys for programming and display control |
| Low-flow cut-off | 0-9.9% |
| Data logging function | 99 Date / time records for alarm |
| Logged data | Date / time of power on/off / 99 Years flow rate / energy / temperature / total flow / total energy Record data every one hour |
| Damping | 0.1-99.9 s |
| Self-diagnostics | The following error messages are displayed if failure occurs – Temperature failure – Temperature abnormal – Empty pipe – EEPROM abnormal |
| Data retention | Operation parameter and totalizer figures are stored by EEPROM for more than 10 years |
| Cable entry | Standard: M20 Option: 1/2" NPTF |
| Ingress protection | IP67 |
| Ambient temperature | -25-65 °C |
| Material | Aluminum alloy |
| Temperature input | PT1000, 2 wires |
| Power supply | 90-260 VAC, 50/60 Hz 24 VDC +/-10% (Option) |
| Power consumption | 10-20 W (Dependent on sensor size) |
| Weight | 4.5 kg |
| Mounting | Bracket on 2" Pipe |